Skip to main content
Home  › ... Store › Product
2.9kW Single-Phase Monitored PDU with LX Platform
Product Type:
Power Supplies
Type Detail:
Server
Manufacturer:
Tripp Lite
Manufacturer #:
PDUMNV30LX
Part Status:
Special Order Only
Milwaukee PC SKU:
301860
Price:
$643.99

PDU Monitored 2.9kW 120V 24 5-15/20R 30A LX Platform 0URM TAA



2.9kW Single-Phase Monitored PDU with LX Platform

The PDUMNV30LX 2.9kW Single-Phase Monitored PDU provides real-time remote monitoring of voltage, frequency and load levels via built-in network connection. Recommended for IT and industrial applications, the vertical PDU features 24 NEMA 5-15/20R outlets with included cord retention brackets to prevent cables from becoming accidentally disconnected. A 10-foot cord with NEMA L5-30P plug connects the PDU to a compatible AC power source, generator or protected UPS. The built-in Java-free HTML5-based LX Platform network interface enables full remote access for PDU status monitoring and email notifications via secure web browser, SNMP, telnet or SSH. It supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network. Optional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring capabilities. Protocols supported include IPv4, IPv6, HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP and NTP. A digital ammeter allows you to monitor power consumption for both breakered load banks, as well as the total load to ensure they remain well below maximum capacity with no danger of overload. The PDU mounts in 0U of space in EIA-standard 19-inch racks using the included toolless mounting buttons or the included rack-mounting brackets. Use the included PDUMVROTATEBRKT kit to install the unit with outlets facing the rear for better airflow or equipment access.


OUTPUT

  • Output Capacity Details: 3.05kW (127V), 2.88kW (120V), 2.4kW (100V) / 30A total capacity (Agency de-rated 24A); 20A max per breakered load bank; 16A max per outlet
  • Frequency Compatibility: 50 / 60 Hz
  • Output Receptacles: (24) 5-15/20R
  • Output Nominal Voltage: 100; 120; 127
  • Overload Protection: Two 20A breakers protect 12 outlets each

INPUT

  • PDU Input: Voltage 100; 120; 127
  • Recommended Electrical Service: 30A 120V
  • Maximum Input Amps 30
  • Maximum Input Amps Details Agency de-rated to 24A continuous
  • PDU Plug Type: NEMA L5-30P
  • Input Cord Length (ft.): 10
  • Input Phase; Single-Phase

USER INTERFACE, ALERTS & CONTROLS

  • Front Panel LCD Display: Digital meter reports PDU output current in amps, Scroll IP-address information; Display can be rotated 180 degrees for installation with the input cable at the top
  • Front Panel LEDs: Front panel LEDs indicate which loading segment the digital LCD current display is reporting; Bank 1 LED indicates the meter is reporting load level for outlets 1-12; Bank 2 LED indicates the meter is reporting load level for outlets 13-24; Both LEDs lighted indicates the meter is reporting load level for all outlets combined
  • Switches: Press the SCROLL IP button and release to display the configured IP address in 2 digit intervals; Press the SELECT / ROTATE button and release after one second to advance the local display power, power consumption for the 3 reported segments: Bank 1, Bank 2 and Banks 1+2; Press the SELECT / ROTATE button and release after two seconds to rotate the display 180 degrees
  • COMMUNICATIONS: SNMP Compatibility - Built-in LX Platform network interface

Product Warranty Period: 2-year limited warranty